Anyone in Austria planning PV storage or backup power systems with Victron needs a 48 V LiFePO₄ battery that communicates cleanly with the GX device via CAN bus, provides the required safety evidence for building and fire regulations, and is available from stock. This technical article summarises for electricians and installers the fundamentals around MultiPlus-II, Cerbo GX, CAN bus, DVCC and IEC 62619:2022 clause 7.3.3.
Involtis is the general importer of Easyway Energy for Austria and supplies specialist businesses only. For Victron systems we supply exclusively our 48 V models from stock in Austria. No claim of official Victron approval, certification or listing.
Why CAN-bus communication is decisive for Victron storage
Inverter/chargers such as the Victron MultiPlus-II are designed for 48 V systems and work together with a GX controller (e.g. Cerbo GX). With managed lithium batteries, communication runs via the battery management system (BMS) over CAN bus. Only through this connection does the battery report its current charge and discharge limits to the GX device.
The UNIV-16kWh(II) manual documents the protocol selection VCTR (Victron) and the CAN interface pin assignment (pin 4: CAN-H, pin 5: CAN-L). The UNIV-16kWh(WP) also communicates via CAN bus and has proven itself in our own Victron installations; we do not have a VCTR protocol entry in the WP manual.
The three building blocks at a glance: MultiPlus-II, Cerbo GX and 48 V battery
- Victron MultiPlus-II (48 V): Multifunctional inverter/charger for grid-parallel ESS systems (Energy Storage System) as well as off-grid and backup systems, scalable in parallel and three-phase.
- GX device (e.g. Cerbo GX): Central communication unit. The MultiPlus-II is connected via the VE.Bus port; the battery BMS is connected via BMS-Can or VE.Can.
- 48 V LiFePO₄ storage (51.2 V): The battery with its own BMS, which monitors cell voltages, temperatures and current limits and reports them to the GX device via CAN bus.
DVCC: how Cerbo GX applies the battery’s limits
DVCC stands for Distributed Voltage and Current Control at Victron. Once DVCC is enabled on the GX device (menu Settings → System setup → Charge control), the GX device takes over active charge control based on the parameters reported by the BMS:
- CVL – Charge Voltage Limit (maximum charge voltage)
- CCL – Charge Current Limit (maximum charge current)
- DCL – Discharge Current Limit (maximum discharge current)
Connected MultiPlus-II units and solar charge controllers follow these BMS limits directly. This keeps the battery within its permitted operating range.
Easyway UNIV 48 V models for Victron systems
Only the 48 V low-voltage batteries of the UNIV series are suitable for Victron systems (51.2 V nominal voltage, 44.8 – 57.6 V voltage range, 314 Ah, 16.08 kWh total energy / 15.11 kWh usable, up to 20 units in parallel):
| Model | Protection rating & interface | Rec. / max. current | Victron relevance | Datasheet |
|---|---|---|---|---|
| UNIV-16kWh(II) | IP20 (indoor), touchscreen, Bluetooth, Wi-Fi opt. | 157 A / 200 A | CAN protocol VCTR documented in the manual; in stock AT | Datasheet DE (PDF) |
| UNIV-16kWh(WP) | IP65, app + Wi-Fi, integrated aerosol fire extinguisher | 157 A / 157 A charge, 200 A discharge | CAN bus, proven in our own Victron installations; in stock AT | Datasheet DE (PDF) |
In our own installation, three Victron MultiPlus-II units work together with six Easyway UNIV batteries in daily operation. An overview of models and availability is on our page Victron compatible batteries (48 V).
Technical points for CAN connection by the installer
Build, cabling and configuration must follow the current Easyway and Victron manufacturer manuals exclusively; installation is carried out by a qualified installer:
- Protocol on the battery: In the Easyway battery menu, the CAN protocol VCTR (Victron) is selected where the respective manual provides for it. For the UNIV-16kWh(II) this selection is documented in the manual.
- Observe the CAN pin assignment: According to the Easyway manual, CAN-H is on pin 4 and CAN-L on pin 5 of the battery’s RJ45 CAN port. On the Victron side there are different cable types (VE.Can to CAN-bus BMS type A and type B) with different pin assignments. The exact assignment must be checked against the current manual before connection.
- GX port & DVCC: The connection is made at the configurable BMS-Can or VE.Can port of the GX device (with a terminating resistor according to the Victron manual). DVCC is enabled in the GX menu so that CVL, CCL and DCL apply system-wide.
Fire safety in Austria: IEC 62619:2022 clause 7.3.3
Especially at larger 48 V storage capacities (e.g. 16 to 96 kWh in a multi-unit setup with MultiPlus-II), Austrian building regulations – for example OIB Guideline 2 (2023) clause 3.9.12 c – require evidence against fire propagation (thermal runaway propagation) above certain thresholds. Notes on the notification duty in Styria under section 21 of the Styrian Building Act (Stmk. BauG) are in our article on the test evidence.
For the four 48 V models UNIV-16kWh, UNIV-16kWh(I), UNIV-16kWh(II) and UNIV-16kWh(WP) the SGS test report SHES260400554801 according to IEC 62619:2022 clause 7.3.3 and CB certificate BE-57990 are available (propagation test passed: no fire outside the enclosure, no rupture of the enclosure). The background for Austrian electricians is explained in our article IEC 62619 clause 7.3.3: what the thermal-runaway evidence means for electricians. The building-law assessment in the individual case is a matter for the competent building authority.
Deye and other inverter brands
Our range focuses on Deye hybrid inverters (as Deye specialists, not an official Deye sales partner): more on this is in Deye hybrid inverters with Easyway storage and on the overview Compatible inverters.
Delivery and availability for installers in Austria
Involtis sells exclusively to specialist businesses – installers, electricians and trade partners. We supply the 48 V models UNIV-16kWh(II) and UNIV-16kWh(WP) directly from stock in Austria and will gladly inform you about lead times and availability.
Frequently asked questions
Which battery suits the Victron MultiPlus-II?
How are Easyway batteries connected to a Victron Cerbo GX?
Are high-voltage batteries suitable for the Victron MultiPlus-II?
What fire-safety evidence is available in Austria?
Can I order from Involtis as a private customer?
Enquiry about models and availability
Are you planning a Victron project and need 48 V batteries from stock in Austria? Enquire about models, quantities and delivery dates directly: Request a quote · Telephone: +43 670 60 52 919 or +43 664 46 111 80.
Sources
- Victron Energy: MultiPlus-II (product page) – retrieved on 25.11.2026
- Victron Energy: Cerbo GX Manual (overview) – retrieved on 25.11.2026
- Victron Energy: Cerbo GX Manual, Chapter 12: DVCC – Distributed Voltage and Current Control – retrieved on 25.11.2026
- Victron Energy: VE.Can to CAN-bus BMS cables manual – retrieved on 25.11.2026
- Easyway Energy / Involtis: Datasheet Easyway UNIV-16kWh(II), freestanding (DE) – checked on 25.11.2026
- Easyway Energy / Involtis: Datasheet Easyway UNIV-16kWh(WP), freestanding (DE) – checked on 25.11.2026
- Easyway Energy: UNIV-14.3kWh / UNIV-16kWh (II) User Manual EN (ch. 3.2.2.3 Protocol Switch “VCTR: Victron”, CAN pin assignment), local manual – checked on 25.11.2026
- SGS-CSTC / SGS Belgium NV (CEBEC): Test Report SHES260400554801 and CB certificate BE-57990 according to IEC 62619:2022 clause 7.3.3 for UNIV-16kWh, (I), (II), (WP), local test report – checked on 25.11.2026